TitleProduct

High Accuracy Portable AC/DC Current Source and Voltage Source

  • Price:

    Negotiable

  • minimum:

  • Total supply:

  • Delivery term:

    The date of payment from buyers deliver within days

  • seat:

    Beijing

  • Validity to:

    Long-term effective

  • Last update:

    2017-12-14 07:34

  • Browse the number:

    228

Send an inquiries

Company Profile

Beijing GFUVE Electronics Co., Ltd.

By certification [File Integrity]

Contact:Mr. Andy Huang(Mr.)  

Email:

Telephone:

Phone:

Area:Beijing

Address:Beijing

Website: http://guangfuhui.chuge88.com/

Product Details

GF6018A high accuracy portable ac/dc current source and voltage source with dc power source


GF6018A high accuracy portable ac/dc current source and voltage source is according to verification regulation JJG124-2005 "ammeter, voltmeter, power meter and resistance meter calibration regulations, JJF1075-2001" clamp ampere ammeter calibration the requirements of the "standards for the design of 0.05 magnitude AC and DC standard units.The source of the signals of the DSP and 16 high-speed digital-to-analog converters can control of the sine wave, distortion wave source.The display USES graphics standard 240 X 128 LCD monochrome screen
Main Functions and Features
1.GF6018A high accuracy portable ac/dc current source and voltage source consists of a single-phase AC voltage standard resource, current standard resource and DC voltage, current standard resource of standard resource.
2.Have calibration function, which can according to the standard of external value, fixed standard resource output values.
3.The setting of the range for verification 1999 (9), 3999 (9) a display of the digital multimeter.
4.Manual and semi-auto inspection 0.2% and below levels of digital multimeter, an analogue meter installation type digital instrument, including DC analog output of digital instrument;All kinds of clamp ampere ammeter;Verification clamp ampere ammeter range for 200 A, 600 A, 1000 A.
5.To generate containing 2 ~ 31 harmonic wave distortion, the harmonic number, number, amplitude and phase of the harmonic wave to base wave all can be programmed control.
6.With RS232 interface and large capacity non-volatile memory, can store 500 blocks are inspection table test data.Through the PC software, the PC control this device automatic and manual inspection, and the results are processing and management.
Technical Data
Electrical parameters
Power supply Single phase AC 220V±10% or 110V±10%, 50/60HzAC
AC Voltage output
range 200mV, 400mV, 2000mV, 4000mV,
20V, 100V, 200V, 500V, 1000V
Range 20V-1000V Accuracy ±(0.03%RD+0.02%FS)
Stability ≤0.01% FS /60s
Range 200mV-4000mV Accuracy ±(0.3%RD+0.2%FS)
Stability ≤0.04% FS /60s
Load capacity 20VA
Waveform distortion ≤0.3%
Adjustable Range 0-120% FS (1000V not included)
Fineness 5×10-5
AC Current Output
Range 2mA, 4mA, 20mA, 40mA, 0.2A, 0.5A, 2A, 5A, 10A, 20A
Range 0.2A-20A Accuracy ±(0.03%RD+0.02%FS)
Stability ≤0.01% FS /60s
Range 2mA-40mA Accuracy ±(0.3%RD+0.2%FS)
Stability ≤0.04% FS /60s
Load capacity 20VA
Waveform distortion ≤0.3%
Adjustable Range 0-120% FS
Fineness 5×10-5
Frequency Output
Range 45-65Hz
Fineness 0.001Hz
Accuracy 0.01Hz
Harmonic Wave
Times 2-31
Extent 0-20%
Each harmonic phase fineness 0.01·N (N is harmonic order)
DC voltage output
Range 200mV, 400mV, 2000mV, 4000mV,
20V, 40V, 100V, 200V, 400V, 1000V
Load capacity 20W
Adjustable range 0-110% FS (1000V not included)
Adjustable fineness 5×10-5
Stability ≤0.01% FS /60s (peak-peak value)
Accuracy ±(0.03%RD+0.02%FS)
Ripple wave ≤1% FS
DC current output
Range 20uA, 40uA, 200uA, 400uA, 2mA, 4mA,
20mA, 40mA, 0.2A, 1A, 2.5A, 5A, 10A, 20A
Load capacity 20W
Adjustable Range 0-110% FS (1000V not included)
Adjustable Fineness 5×10-5
Stability ≤0.01% FS /60s (peak-peak value)
Accuracy ±(0.06%RD+0.04%FS)
Ripple wave ≤1% FS
Resistance box
Range 0-200Ω, 200-400Ω, 0-2kΩ, 2kΩ-4kΩ, 0-20kΩ, 20kΩ-40kΩ,
0-200kΩ, 200kΩ-400kΩ, 0-2MΩ, 2MΩ-4MΩ
Fineness 0.02%
Range 0-2kΩ, 0-20kΩ, 0-200kΩ
Range 0-2kΩ Adjustable Range 0-100%FS
Accuracy ±(0.12%RD+0.08%FS)
Range 0-200Ω,0-2MΩ Adjustable Range 0-100% FS
Accuracy ±(0.3%RD+0.2%FS)
Range 2kΩ-4kΩ, 20kΩ-40kΩ, 200kΩ-400kΩ
Range 2kΩ-4kΩ Adjustable Range 5%-100%FS
Accuracy ±(0.12%RD+0.08%FS)
Range 200-400Ω,
2MΩ-4MΩ
Adjustable Range 5%-100% FS
Accuracy ±(0.3%RD+0.2%FS)
Clamp meter range
200A Accuracy ±0.2%
600A Accuracy ±0.5%
1000A Accuracy ±1%
Dot frequency square wave output
Range 1kHz, 5kHz, 10kHz, 50kHz, 100kHz, 200kHz, 1000kHz
Square wave amplitude 4.5V
Setting accuracy 5×10-5
Mechanical parameters
Dimension (L×W×H) (mm) 440x360x160
Weight (kg) 12
Environmental conditions
Operating temperature 20°C±10°C
Relative humidity ≤85%RH